13
4.0 INSTALLATION
Table 2B: Refrigerant Line Sizing Chart (Metric Units)
< 8 8-15 16-23 24-30 31-38 39-46
6.35 [1/4]
15.88 [5/8] n/a 8 / 0.99 15 / 0.98 9 / 0.97 1 / 0.97 NR NR
7.94 [5/16] 15.88 [5/8] 22 8 / 0.99 15 / 0.98 15 / 0.97 15 / 0.97 15 / 0.96 15 / 0.95
9.53 [3/8] 15.88 [5/8] 15 8 / 0.99 15 / 0.99 15 / 0.97 15 / 0.97 15 / 0.96 15 / 0.95
6.35 [1/4] 19.05 [3/4] * n/a 8 / 1.00 15 / 0.99 9 / 0.99 1 / 0.99 NR NR
7.94 [5/16] 19.05 [3/4] * 22 8 / 1.00 15 / 0.99 15 / 0.99 15 / 0.99 15 / 0.98 15 / 0.98
9.53 [3/8] 19.05 [3/4] * 15 8 / 1.00 15 / 0.99 15 / 0.99 15 / 0.99 15 / 0.98 15 / 0.98
7.94 [5/16] 15.88 [5/8] 6 8 / 0.99 15 / 0.97 15 / 0.95 15 / 0.93 10 / 0.91 NR
9.53 [3/8] 15.88 [5/8] 5 8 / 0.99 15 / 0.97 15 / 0.95 15 / 0.93 15 / 0.91 NR
7.94 [5/16] 19.05 [3/4] 6 8 / 1.00 15 / 0.99 15 / 0.99 15 / 0.98 10 / 0.97 5 / 0.96
9.53 [3/8] 19.05 [3/4] 5 8 / 1.00 1
5 / 0.99 15 / 0.99 15 / 0.98 15 / 0.97 15 / 0.96
12.7 [1/2] 19.05 [3/4] 0 8 / 1.00 15 / 0.99 15 / 0.99 15 / 0.98 15 / 0.97 15 / 0.96
9.53 [3/8] 19.05 [3/4] 0 8 / 0.99 15 / 0.98 15 / 0.97 15 / 0.95 15 / 0.94 15 / 0.93
12.7 [1/2] 19.05 [3/4] 0 8 / 0.99 15 / 0.98 15 / 0.97 15 / 0.95 15 / 0.94 15 / 0.93
9.53 [3/8] 22.23 [7/8] 0 8 / 1.00 15 / 0.99 15 / 0.99 15 / 0.98 15 / 0.98 15 / 0.97
12.7 [1/2] 22.23 [7/8] 0 8 / 1.00 15 / 0.99 15 / 0.99 15 / 0.9
8 15 / 0.98 15 / 0.97
9.53 [3/8] 19.05 [3/4] 0 8 / 0.99 15 / 0.97 15 / 0.95 15 / 0.93 15 / 0.91 NR
12.7 [1/2] 19.05 [3/4] 0 8 / 0.99 15 / 0.97 15 / 0.95 15 / 0.93 15 / 0.91 NR
9.53 [3/8] 22.23 [7/8] 0 8 / 1.00 15 / 0.99 15 / 0.98 15 / 0.98 15 / 0.97 12 / 0.96
12.7 [1/2] 22.23 [7/8] 0 8 / 1.00 15 / 0.99 15 / 0.98 15 / 0.98 15 /0.97 15 / 0.96
Notes:
1) Do not exceed 46 meters linear line length.
2) *Do not exceed 15 meters vercal separ
aon between indoor and outdoor units if the indoor unit is above the indoor unit.
3) ** 19.05mm [3/4 in.] vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor
unit to assure proper oil return.
4) Always use the smallest liquid line allowable to minimize refrigerant charge.
5) Applicaons shaded in light gray indicate capacity mulpliers between 0.90 and 0.96 which are not
recommen
ded, but are allowed.
6) Applicaons shaded in dark gray are not recommended due to excessive liquid or sucon pressure drop.
7.0 KW
[2.0 Ton]
** SEE
NOTE 3
10.6 KW
[3 Ton]
14.1 KW
[4 Ton]
17.6 KW
[5 Ton]
17 SEER 2-Stage Air-Condioners
Unit Size
Allowable
Liquid Line
Size
mm [in.]
Allowable
Vapor Line
Size
mm [in.]
Outdoor Unit ABOVE or BELOW Indoor Unit
Equivalent Length (Meters)
Maximum Vercal Rise (Outdoor Unit Below Indoor Unit) * / Capacity Mulplier
Guidelines for
Linear Line
Lengths
Greater
Than Shown