64
Parameter Description
01 t0 Minimum safety temperature. The value
can be set from 1°C to 5°C.
Default set to 3°C.
Should the BeSMART room probe detect
a temperature below the parameter set, a
heating request is generated – only when
HEATING in operating modes SUMMER/
DOMESTIC HOT WATER and OFF – taking
into account the hysteresis set under the
HOn and HOFF parameters.
ESC
MODE
08 HHCH Maximun local central heating temperature
setpoint (available with OTBus connection
between the WiFi Box and the boiler or the
RF receiver and the boiler or the BeSMART
and the boiler, if provided for by the OTBus
protocol).
The value can be set between 80°C and
40°C (for high temperature heating) or from
45°C to 20°C (for low temperature heating).
ESC
MODE
08 LLCH
Minimum heating setpoint temperature (avail
-
able with OTBus connection between the WiFi
Box and the boiler or the RF receiver and the
boiler or the BeSMART and the boiler, if pro
-
vided for by the OTBus protocol).
The value can be set from 10°C to HHCH -1°C.
ESC
MODE