Parameter Description
10 CLI Thermoregulation curve with external probe
connected to the boiler or external web
probe via the APP (available with OTBus
connection between the WiFi Box and the
boiler or the RF receiver and the boiler or
the BeSMART and the boiler, if provided for
by the OTBus protocol).
Default set to 1.2°C.
The value can be set from 0.2°C to 3°C.
The parameter in question affects the cal
-
culation of the heating delivery setpoint
temperature.
T Mand risc = T Mand Curva + ( CLI * InFL * ΔT Amb)
T Mand Curva = Delivery temperature calculated using the thermoregula
-
tion curve set under parameter CLI
CLI = thermoregulation curve
InFL = room influence
ΔT Amb = (room temperature set) – (current room temperature)