15
ELECTRICAL SYSTEM
Figure 17
Initials Jumper N. Description
S1 J11 (1-2) Flow temp. probe (HT)
SB J11 (3-4) Water tank temp. Probe
S2 J11 (5-6) Flow temp. probe (LT)
SE J11 (7-8) External temp. Probe
T2 J12 (9-10) Room thermostat (HT)
T2 J12 (11-12) Room thermostat (LT)
AI J12 (13-14) 0-10V analogic device
CR J12 (15-17) Remote control
AL J8 (18-19) Alarm signal
VM J9 (20-22) Mixer valve
P4 J10 (23-24) LT system circulator
P1 J10 (25-26) HT system circulator
P2 J10 (27-28) Hot water circulator
Figure 18
Correspondence table for all sensors
Measured temperatures (°C) - Resistive values of the sensors (Ω).
T (°C) R (°Ω) T (°C) R (°Ω) T (°C) R (°Ω) T (°C) R (°Ω) T (°C) R (°Ω) T (°C) R (°Ω) T (°C) R (°Ω)
- 20 67739 - 1 28481 18 13062 37 6470 56 3426 75 1925 94 1137
- 19 64571 0 27279 19 12565 38 6247 57 3319 76 1870 95 1108
- 18 61568 1 26135 20 12090 39 6033 58 3216 77 1817 96 1079
- 17 58719 2 25044 21 11634 40 5828 59 3116 78 1766 97 1051
- 16 56016 3 24004 22 11199 41 5630 60 3021 79 1717 98 1024
- 15 53452 4 23014 23 10781 42 5440 61 2928 80 1669 99 998
- 14 51018 5 22069 24 10382 43 5258 62 2839 81 1622 100 973
- 13 48707 6 21168 25 9999 44 5082 63 2753 82 1577 101 948
- 12 46513 7 20309 26 9633 45 4913 64 2669 83 1534 102 925
- 11 44429 8 19489 27 9281 46 4751 65 2589 84 1491 103 901
- 10 42449 9 18706 28 8945 47 4595 66 2512 85 1451 104 879
- 9 40568 10 17959 29 8622 48 4444 67 2437 86 1411 105 857
- 8 38780 11 17245 30 8313 49 4300 68 2365 87 1373 106 836
- 7 37079 12 16563 31 8016 50 4161 69 2296 88 1336 107 815
- 6 35463 13 15912 32 7731 51 4026 70 2229 89 1300 108 796
- 5 33925 14 15289 33 7458 52 3897 71 2164 90 1266 109 776
- 4 32461 15 14694 34 7196 53 3773 72 2101 91 1232 110 757
- 3 31069 16 14126 35 6944 54 3653 73 2040 92 1199
- 2 29743 17 13582 36 6702 55 3538 74 1982 93 1168