EasyManuals Logo

Riello Condexa Pro3 Series User Manual

Riello Condexa Pro3 Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
18
FIRST OPERATING
7 FIRST OPERATING
To complete the start-up of the boiler, the following operations
are necessary, that should only be performed by an authorized
Service
R:
verication of the installation;
slave board setting
combustion analysis.
7.1 Slave board setting
This operation that should only be performed by an authorized
Technical Assistance Service
R.
Each slave unit that composes the system should be identia-
ble from the only master board, through an address that is as-
signed properly conguring the switches J10 and J17, on each
slave battery. Each slave (one for each burner) needs to be prop-
erly congured so that the Master board shall detect their right
sequence.
The slaves are divided into blocks of four slave each (every Con-
dexa Pro3 IN-EXT is a block) and the system can handle up to
15 blocks.
Therefore, the address conguretion is done for each slave us-
ing the following procedure, always remembering that a block
is equivalent to a unit:
locate the block the slave is related to (ex. block n°1, n°2,
etc., till block n°15);
locate the slave position inside each block (e.g. posi-
tion1,2,3 or 4);
supply each Condexa Pro3 IN-EXT composing the battery
(see par.6.4.1).
9
Qualied personnel only may work on the electrical system
and in compliance to provisions of the law, with particular
attention to rules on safety.
As shown in Figure 24to set the address of the block you should
work on the switch located on the right (Jumper J17) and for
each slave (single burner) on the Left one (Jumper J10).
Figure 24
Refer to the table to see the possible combinations of the jump-
ers J10 that characterize the four slaves (n 1, 2, 3 and 4) of the
same block.
JUMPER J10
SLAVE ADDRESS
1 2
OFF OFF 1
OFF ON 2
ON OFF 3
ON ON 4
Following table shows the possible combinations of the jumpers
(J17) we have the settings for the maximum (15) number of block.
JUMPER J17
4 UNITS BLOCK
(unit)
1 2 3 4
OFF OFF OFF OFF Emergency
OFF OFF OFF ON 1° block
OFF OFF ON OFF 2° block
OFF OFF ON ON 3° block
OFF ON OFF OFF 4° block
OFF ON OFF ON 5° block
OFF ON ON OFF 6° block
OFF ON ON ON 7° block
ON OFF OFF OFF 8° block
ON OFF OFF ON 9° block
ON OFF ON OFF 10° block
OFF OFF ON ON 11° block
ON ON OFF OFF 12° block
ON ON OFF ON 13° block
ON ON ON OFF 14° block
ON ON ON ON 15° block
The data have to be used regardless of the number of units
present: if, for example, have 6 blocks in the battery we will
consider combinations until the line corresponding to the 6th
block, and not beyond.
In the following part is an example of conguration of a battery
with seven burner in cascade.
7.1.1 Example of conguretion of a battery with 7
burner in cascade
In case two blocks are present in an installation having a battery
of seven burners (i.e. seven slaves): the rst is made of 4 burn-
ers and the second is made of 3. As a consequence, two blocks
need to be congured, respectively with address 1 and 2 and
with relative burners, to the rst block with address 1,2,3 and 4,
and to the second block with address 1,2 and 3 (see Figure 25).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Riello Condexa Pro3 Series and is the answer not in the manual?

Riello Condexa Pro3 Series Specifications

General IconGeneral
BrandRiello
ModelCondexa Pro3 Series
CategoryBoiler
LanguageEnglish

Related product manuals