2. WIRING
IMCB03-E4
3
When host computer interface is RS-485
It is necessary that a circuit to transfer send and receive be built-in the host computer.
SG
T/R
B
T/R
A
SG
T/R
B
T/R
A
RD (RXD)
:
Receive data
SD
TXD
:
Send data
Host com
uter
RS-485
SG
T/R
B
T/R
A
U
to 31
Paired wire
Send/receive
selection signal
Twisted pair wire
(with shield)
*R: Termination resistors (Example: 120
Ω
1/2 W)
*R
Controller
Controller
SD (TXD) and RD (RXD): Negative logic
*R
When host computer interface is RS-232C
RS-232C/RS-485 converter is required.
Controller
SG
T/R(B)
T/R(A)
RS-485
SG
T/R(A)
T/R(B)
RS-232C
Host computer
RS-232C/RS-485
converter
Twisted pair wire
(with shield)
Paired wire
*R: Termination resistors (Example: 120
Ω
1/2 W)
*R *R
When the host computer use Windows 95/98/NT, use a RS-232C/RS-485 converter with an
automatic send/receive transfer function.
Recommended: CD485, CD485/V manufactured by Data Link, Inc. or equivalent.
CAUTION