5. COMMUNICATION IDENTIFIERS
IMSRM04-E8
39
Continued from the previous page
Name
Iden-
tifier
Digits
Attri-
bute
Data range
Factory
set
value
Refer-
ence
page
Deadband/Overlap
V1
6 R/W -10.0 to +10.0 % of span 0.0 54
Control response
parameters
CA
1 R/W 0: Slow 1: Medium
2: Fast
*1 55
First alarm set value
A1
6 R/W Within input range or span
range
*2 56
Second alarm set value
A2
6 R/W Within input range or span
range
*2
Heater break alarm
(HBA) set value 1
A3
6 R/W 0.0 to 100.0 A or
0.0 to 30.0 A (For the CT
input of the TIO module)
0.0 43
Heater break alarm
(HBA) set value 2
A4
6 R/W 0.0 to 100.0 A or
0.0 to 30.0 A (For the CT
input of the CT module)
0.0
Operation mode transfer
EI
1 R/W 0: Unused 1: Monitoring
2: Alarm 3: Normal
357
Heat-side proportioning
cycle
T0
6 R/W 1 to 100 sec.
(Setting will be invalid in
continuous output of
current/voltage.)
*3 58
Cool-side proportioning
cycle
T1
6 R/W 1 to 100 sec.
(Setting will be invalid in
continuous output of
current/voltage and heat
action.)
*3
PV bias
PB
6 R/W -5.00 to +5.00 % of span 0.00 59
Control Run/Stop
SR
1 R/W 0: Stop 1: Run 1 60
Initialize setting mode
IN
1 R/W 0: Normal communication
1: Extended communication
061
Memory area number
ZA
1 R/W Number 1 to 8 1 62
Alarm interlock release
AR
1 WO 1: Release (1 only)
−
63
Auto/Manual transfer
J1
1 R/W 0: Auto 1: Manual 0 64
Manual output value
ON
6 R/W -5.0 to +105.0 % 0.0
: Memory area response settings group (See page 62) Continued on the next page.