4. BASIC OPERATION
IMR02L04-E3
4-35
Continued from the previous page.
Name Symbol Data range
Factory set
value
Function block 23 (F23.01, F23.02)
Digital input (DI) assignment
DISL
0 to 5
DI1 to DI6 (Optional)
Based on
model code.
When not
specifying: 0
DI1 DI2 DI3 DI4 DI5 DI6
0 PTN1 PTN2 PTN4 PTN8 PTN16 P.SET
1 PTN1 PTN2 PTN4 PTN8 PTN16 P.SET
2 WAIT WAIT WAIT WAIT WAIT WAIT
3 WAIT WAIT WAIT WAIT WAIT WAIT
4 WAIT WAIT WAIT WAIT WAIT WAIT
5 WAIT WAIT WAIT WAIT WAIT WAIT
DI7 to DI11 (Standard)
DI7 DI8 DI9 DI10 DI11
0 RESET RUN STEP HOLD PTN32
1 RESET RUN STEP PTN32 PTN64
2 PTN1 PTN2 PTN4 PTN8 P.SET
3 PTN1 PTN2 PTN4 PTN8 PTN16
4 RESET RUN STEP HOLD D/R
5 RESET RUN STEP HOLD
PTN_INC
PTN1 to PTN64: Pattern number switch
P.SET: Pattern set
WAIT: Wait state release
RESET: Reset mode setting
RUN: Program control mode setting
HOLD: Hold function
STEP: Step function
D/R: Direct/Reverse action switching
PTN_INC Pattern increment
Pattern input method of Digital input
(DI)
DIPTN
0: Set Pattern number by using the Pattern set input.
Pattern number Binary number of DI 1
1: Set Pattern number by switching the contact input.
Pattern number Binary number of DI 1
2: Set Pattern number by using the Pattern set input.
Pattern number Binary number of DI
3: Set Pattern number by switching the contact input.
Pattern number Binary number of DI
To change Pattern number, refer to Pattern number
switch of the PF900/PF901 Instruction Manual
(IMR02L03-E) on the CD-ROM.
0
Function block 30 (F30.01 to F30.08)
OUT2, OUT3
Energized/De-energized
EXOUT
0: Energized 1: De-energized
00000 Value at SV display
OUT2
OUT3
Unused
00
DO1 to DO4
Energized/De-energized
EXDO1
0: Energized 1: De-energized
00000 Value at SV display
DO1
DO2
DO3
DO4
Unused
0000
DO5 to DO8
Energized/De-energized
EXDO2
0: Energized 1: De-energized
00000 Value at SV display
DO5
DO6
DO7
DO8
Unused
0000
Continued on the next page.