Beacon 410 Gas Monitor Operator’s Manual Viewing and Changing Global Parameters • 35
RELAYS ABCD used as
(COMMON ALARM RELAYS)
If set to COMMON ALARM RELAYS, relays A, B, C, and D are
defined as common alarms assigned to the gas alarms as follows:
Relay A: Common Alarm 1
Relay B: Common Alarm 2
Relay C: Common Alarm 3
Relay D: Common Any alarm
If set to CHANNEL ALARM RELAYS, relays A, B, C, and D are
defined as configurable channel alarm relays assigned to the
detection channels as follows:
Relay A: Channel 1
Relay B: Channel 2
Relay C: Channel 3
Relay D: Channel 4
Each relay is factory assigned to alarm 3, but this can be changed
in the Configuration Menu.
BUZZER SILENCE
(CAN SILENCE BUZZER)
If set to CAN SILENCE BUZZER, the buzzer can by silenced by
pressing and releasing the reset switch when the Beacon 410 is in
a gas alarm condition.
If set to CAN”T SILENCE BUZZEZR, the buzzer cannot be
silenced by the reset switch while the Beacon 410 is in a gas
alarm condition.
Table 6: Global Menu Parameters (Continued)
Global Parameter
(Factory-Set Value)
Description