14
INSTALLER SETUP
Settings Display Adjustment Options Default
Cooling Fan
Delay
The cooling fan delay setting delays
the fan from coming on in cool
mode and keeps it running after
the compressor shuts off for a
short time in order to save energy.
The cooling fan delay can be set
to OFF, 15, 30, 60 or 90 seconds.
If 15, 30, 60 or 90 is selected, the
fan will not turn on for at least the
selected time when there is a call
for cool and will run for at least the
selected time after satisfying the
call for cool.
OFF
Heating
Temperature
Set-Point
Limit
This setting establishes a maximum
value above which the set-point
temperature value cannot be raised.
Use or to select
the maximum heat temperature
set-point. The maximum heat
temperature set-point is 90°F.
Range 44°F - 90°F
90°
Cooling
Temperature
Set-Point
Limit
This setting establishes a maximum
value above which the set-point
temperature value cannot be
lowered.
Use or to select
the maximum cool temperature
set-point. The minimum cool
temperature set-point is 44°F.
Range 44°F - 90°F
44°
F° or C°
Select F for Fahrenheit temperature
display or select C for Celsius
display.
°F for Fahrenheit
°C for Celsius
F OR C SET