Rockwell Automation Publication 2080-UM002L-EN-E - November 2021 159
Chapter 10 Using microSD Cards
Backup and Restore Directory Structure
When a user project is backed up, a subdirectory named
<Micro800>\USERPRJ is created on the microSD card. The folder name takes
the name of the project specified in the General Page in the Connected
Components Workbench software, which is the name of the controller by
default. However, if the ConfigMeFirst.txt file specifies a different
subdirectory (example: MyProject), the project is backed up to that directory.
See General Configuration Rules in ConfigMeFirst.txt
on page 162.
Project restore is done from the subdirectory specified in ConfigMeFirst.txt
file or the <Micro800>/USERPRJ default folder, if none is specified in the
ConfigMeFirst.txt file. The user needs to ensure that the directory is populated
with correct contents before restoring.
The ConfigMeFirst.txt file is a configuration file stored on the microSD card
that the user can optionally create to customize backup, restore, recipe, and
Method Backup Restore
Online with Connected Components
Workbench software
Yes Yes
Project configuration on memory
card at power-up
No
Load Always and/or Load on Memory
Error options
ConfigMeFirst.txt at power-up
Yes
(Through the [BKD] command)
Yes
(Through the [RSD] command)