EasyManuals Logo

Rockwell Automation Allen-Bradley PowerFlex 700 Series User Manual

Rockwell Automation Allen-Bradley PowerFlex 700 Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26 Rockwell Automation Publication 750-QS100B-EN-P - August 2020
Step 3: Power Up, Configure the Modular Control Profiles
Configure Embedded EtherNet/IP Communication Adapter
If you are using a communication adapter, configure the address so that it corresponds to the data collected in Tabl e 2 on
page 10.
If you are using a communication option module (20-750 series), refer to the appropriate 750COM-UM user manual for
more information about setting communication addresses.
See PowerFlex Drives with TotalFORCE Control Built-in EtherNet/IP Adapter User Manual, publication 750COM-
UM009, for more information about configuring the embedded EtherNet/IP adapter.
Active IP addresses are shown in the diagnostic items, parameters 0:49…60.
There are three methods for configuring the embedded EtherNet/IP IP address in the adapter:
1. Adapter Rotary Switches - Use the switches when working on a simple, isolated network (for example,
192.168.1.xxx). The three adapter switches are read when the drive powers up, and represent three decimal digits
from top to bottom (see Figure 3 on page 27
).
a. Set the rotary switches to a valid address (001-254) corresponding to the data collected in Ta b le 2
. The adapter
uses that value as the lower octet of its IP address (192.168.1.xxx, where xxx = rotary switch settings), along
with a subnet mask of 255.255.255.0. No gateway is configured. Also, the setting for adapter parameter 0:300
[Net Addr Sel] is automatically ignored.
b. To accept the changes to IP address switches, perform a Reset Device procedure. See Appendix A > Reset
Device on page 53 for more information.
2. BOOTP or DHCP Server - If you prefer to control the IP addresses of devices using a server, use BOOTP/
DHCP. The IP address, subnet mask, and gateway addresses are then provided by the BOOTP/DHCP server. If
the address is invalid, DHCP is used.
3. Adapter Parameters - Use adapter parameters when you want more flexibility in configuring the IP address, or
when you must communicate outside the control network using a gateway. When adapter parameters are used, the
IP address, subnet mask, and gateway addresses come from the adapter parameters you set.
a. Set the adapter rotary switches to 999. See Figure 3
and its accompanying table for all possible switch settings
and their related descriptions.
b. Navigate to parameter 0:300 [Net Addr Sel]. Press the EDIT soft key. Edit to a value of 1 'Parameters'. Press the
ENTER soft key.
c. Navigate to parameters 0:302…305 [IP Addr Cfg 1…4]. Press the EDIT soft key. Edit the value of each IP
address octet corresponding to the data collected in Table 2
. Press the ENTER soft key. For example, to set the
IP address to 10.20.3.123, you would set the parameters as follows:
0:302 [IP Addr Cfg 1] = 10
0:303 [IP Addr Cfg 2] = 20
0:304 [IP Addr Cfg 3] = 3
0:305 [IP Addr Cfg 4] = 123

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 700 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 700 Series and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 700 Series Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 700 Series
CategoryDC Drives
LanguageEnglish

Related product manuals