Rockwell Automation Publication 280E-PM001A-EN-P – August 2011 59
ArmorStart
®
EtherNet/IP
Communications & Control Programming Manual Chapter 5
k. Parameter 140 sets the rate of deceleration for all speed decreases by
setting the deceleration time in seconds. Set parameter 140 to 25
seconds.
8. Click the Set button to apply the parameters. If the Set button is not
pushed then the parameter values will revert back to the previously set
values when you exit the Properties menu.
9. Attempt to enter a parameter value that is outside the allowed range by
setting parameter 131 to 600. The following warning screen should appear.
Click OK to clear this screen and return to the Parameters menu to set the
parameter within the allowed range.