20 MicroLogix™ 1500 Programmable Controller Base Units
Publication 1764-IN001B-EN-P
Table 14 Working Voltage
Specification 1764-L24AWA
Power Supply Input to Backplane
Isolation
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Verified by one of the following dielectric tests: 151V
ac for 1 second or 2145V dc for 1 second
132V Working Voltage (IEC Class 2 reinforced
insulation)
Output Group to Backplane Isolation Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Output Group to Output Group Isolation Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation).
Specification 1764-24BWA
Power Supply Input to Backplane
Isolation
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Power Supply User 24V Output to
Backplane Isolation
Verified by one of the following dielectric tests: 600V
ac for 1 second or 848V dc for 1 second
50V Working Voltage (IEC Class 2 reinforced
insulation)
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
Output Group to Backplane Isolation Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation).
Output Group to Output Group Isolation. Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation MicroLogix 1500 and is the answer not in the manual?

Rockwell Automation MicroLogix 1500 Specifications

General IconGeneral
BrandRockwell Automation
ModelMicroLogix 1500
CategoryController
LanguageEnglish

Related product manuals