MC16 Operating Manual 09.01.2020
19/52
Parameter Function enables to select function for the Input. The list of all available functions is given in
the table 5 below.
Parameter Parameter specifies parameter of selected function. It is available for some functions only.
Option Register Action Event when the option is enabled then input triggering generates event related to
input function.
Parameter Logic Function specifies logic function for the input. Available values:
OR default value. Target object of the function is activated when at least single input with the
function is triggered.
I value is available only for toggle type inputs. Target object is activated when all inputs with the
function are triggered.
Area Authentication and Authorisation Options
Option User authentication required when the option is enabled then users can trigger the input without
Authorisation(s) assigned. It is enough that such users are equipped with Authentication Factors which are
enrolled in the system.
Option Authorisation for Access Point required when the option is enabled then only users with proper
Authorisation can trigger the input. The Authorisation must include Access Point type Positive rule for the
Access Point where the function is started.
Option Authorisation for Object required when the option is enabled then only users with proper
Authorisation can trigger the input. The Authorisation must include Object type Positive rule for the object of
the function.
Option Authorisation for Function Parameter required when the option is enabled then users with
proper Authorisation can trigger the input. The Authorisation must include Parameter type Positive rule for
the parameter of the function.
Input functions
Input functions are available within selected objects. For example, input line can be used for
arming/disarming and then it should be configured on the level of Alarm Zone. Some of input functions can
be used within Login Options on the level of Access Point.
Input functions are divided into event type which are triggered by pulse and toggle (status) type which are
monitored in regard of their triggering and releasing.