NO - means the input is NORMALLY OPEN, triggered by "ground" (GND). In case of inputs I7, I8 can
be triggered by "ground" (GND) or "plus" (+ VDC).
NC - means the input is NORMALLY CLOSED, triggered by disconnection from "ground" (GND). In
case of inputs I7, I8 can be triggered by "ground" (GND) or "plus" (+ VDC).
OFF - disables the input regardless of other input settings.
• TYPE:
INFO - the input trigger does not trigger an alarm action but initiates the sending of SMS and VOICE
voice calls according to the settings.
24h - the input generates an alarm in each module state and generates the process of sending SMS
and VOICE voice calls according to the settings.
NORMAL - the line triggers an alarm (noisy) if the system is in standby mode and generates the
process of sending SMS and VOICE voice calls according to the settings.
ON / OFF - zone for arming / disarming system. The input can operate in the bistable mode (switch):
the violation arises armed, the end of the violation turns off or monostable (the button when enabled
option: LINE OF PULSE) the action is then: the first violation will arm the module, the second violation
disarms, alternate.
NORMAL SILENT - the input only works in standby mode, it does not generate a loud alarm, it only
generates the process of sending SMS and VOICE voice calls according to the settings.
• DELAY: input delay time unit: [ms], [s],
• TIME DELAY: value of time after which input violation is detected: units [ms] - milliseconds (1s =
1000ms), [s] - seconds.
Example:
• Lock to [min]:
Lock time of input (response) after first violation. This option works for TYPE input: INFO, NORMAL,
NORMAL. For each input you can set the lock time independently (default set to 0s). Min / max =
1min./360min
Warning:
- This option is used to limit the number of notifications and motion detectors connected to the
inputs. limiting the number of transmissions from a given source, readability of transmitted
messages,
- for a motion detector such as PIR, the parameter should be a loud alarm or a minimum of 1
minute.
User can not block: The user can not block input from the application: RopamBasic, RopamDroid or
SMS command.