yyyy tempb xx
Set threshold b for thermostat
1111 tempb 25
Set the value of 25ºC as the "b" value of the thermostat
Remote configuration: OTHER SETTINGS.
Parametr
Opis
Przykład
Uwagi
yyyy lock x
Lock inputs (enter input no.)
1111 lock 2
X number of input
yyyy unlock x
Unlock inputs (enter input no.)
1111 unlock 5
X number of input
yyyy zones
Returns the state of the module inputs.
1111 zones
yyyy downloading x
Remote on / off of the GPRS programming
function
1111 downloading
X = 1 ON
X = 2 OFF
yyyy code zzzz
Change of SMS code (zzzz = new
access code)
1111 code 1234
yyyy - current SMS code
zzzz = new SMS code
yyyy time yy, mm, dd,
hh, mm
Setting, changing date and time
(Yy, mm, dd, hh, mm = year, month, day,
hour, minute)
1111 time 02, 01,
01, 12, 05
After commas, required spacing (space)
yyyy restart
Restart of BasicGSM 2
1111 restart
yyyy status
System status inquiry
1111 status
The device sends a message containing data according to
configuration (eg date, supply status, input state, other
information configured in BasicGSM Manager)
yyyy replysms
Remote on / off
SMS text message confirmation function
1111 replysms 1
X = 1 function enabled
x = 0 function disabled
yyyy ai1a
Analog input ai1 treshold a setting
1111 ai1a 1000
If the input is set to voltage mode - the setting range is 0-
10000mV,
If the input is set to current loop mode - the setting range
is 4-20mA
yyyy ai1b
Analog input ai1 treshold b setting
1111 ai1b 1500
If the input is set to voltage mode - the setting range is 0-
10000mV,
If the input is set to current loop mode - the setting range
is 4-20mA
yyyy ai2a
Analog input ai2 treshold a setting
1111 ai2a 1800
If the input is set to voltage mode - the setting range is 0-
10000mV,
If the input is set to current loop mode - the setting range
is 4-20mA
yyyy ai2b
Analog input ai2 treshold b setting
1111 ai2a 5670
If the input is set to voltage mode - the setting range is 0-
10000mV,
If the input is set to current loop mode - the setting range
is 4-20mA
yyyy events
Request to retrieve the history of the last
7 events from the module
1111 events
yyyy arm
Arming the module
1111 arm
yyyy disarm
Disarming the module
1111 disarm
yyyy echo
Remote on / off
The function of sending unrecognized
SMS messages from the ECHO network,
eg www account passwords, network
information
1111 echo 1
X = 1 function enabled
x = 0 function disabled
yyyy email
Adding an email address to the first free
spot in the user list.
1111 email user@example.com
Provide a valid e-mail account to receive notifications from
the module.
yyyy ussd
Request to use the USSD code to verify
the SIM card account in the module
yyyy USSD *124*#
1111 ussd (code ussd - eg Check account status , e.t.c.)
yyyy outs
Enable binary outputs
yyyy outs 0101
0 = disable, 1 = enabled
yyyy connect
Request a service connection with the
Ropam Bridge server and the BasicGSM
Manager
1111 connect
Yyyy sms code