EasyManua.ls Logo

Rosslare AC-225? AC-225IP? AC-225U - Page 21

Rosslare AC-225? AC-225IP? AC-225U
45 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input and Output Requirements
Normally Open Supervised Double Resistor Input Connection
Connect a 2.2K resistor in series to the input switch contacts.
Connect an 8.2K resistor parallel to the input switch contacts.
Normally Open Supervised Input has 3 states:
1) Switch Open - Normal State:
Loop resistance = 10.4K.
2) Switch Closed – Abnormal State:
Loop resistance = 2.2K.
3) Open circuit (Infinite loop resistance) or short circuit (0
resistance) across input terminals - Trouble State.
Figure 11: Normally Open Supervised Input (Double Resistor)
AC-225 Hardware Installation and User Guide Page 20