EasyManua.ls Logo

Rosslare AC-225? AC-225IP? AC-225U - Inputs Description

Rosslare AC-225? AC-225IP? AC-225U
45 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input and Output Requirements
Normally Closed Supervised Single Resistor Input Connection
Connect a 2.2K resistor in series to the input switch contacts.
Normally Closed Supervised Input has 3 states:
Switch Closed - Normal State:
Loop resistance = 2.2K.
Switch Open – Abnormal State:
Loop resistance = Infinite (open circuit).
Short circuit across input terminals - Trouble State:
Loop resistance = 0 (short circuit).
Figure 12: Normally Closed Supervised Input (Single Resistor)
Normally Closed Supervised Double Resistor Input Connection
Connect a 2.2K resistor in series to the input switch contacts.
Connect an 8.2K resistor parallel to the input switch contacts.
Normally Closed Supervised Input has 3 states:
Switch Closed - Normal State:
Loop resistance = 2.2K.
Switch Open – Abnormal State:
Loop resistance = 10.4K.
AC-225 Hardware Installation and User Guide Page 21