6 x Operation
88
FA ROTEX HeatPumpSolarUnit - Part 2 - 05/2009
Tab. 6-1 Authorisation levels for keys on the user interface
[1] - Weather-dependent target value regulation
The target settings in the parameter settings determine the specified values to be attained in weather-dependent operation.
If the "Weather-dependent target value regulation" is active, the water temperature is determined automatically depending on
the outside temperature: Colder outside temperatures result in warmer water and vice versa. During "Weather-dependent target
value regulation" , the user can adjust the target water temperature by a maximum of 5 °C up or down.
The following setting options are available:
– [1-00] Lowest ambient temperature (Lo_A): Lowest outside temperature.
– [1-01] Highest ambient temperature (Hi_A): Highest outside temperature.
– [1-02] Target value at lowest ambient temperature:
Target temperature at water outlet of the Indoor Module (RKHB) if the outside temperature is equal to or falls below the
lowest ambient temperature (Lo_A).
– [1-03] Target value at highest ambient temperature:
Target temperature at water outlet of the Indoor Module (RKHB) if the outside temperature is equal to or increases above
the highest ambient temperature (Hi_A).
key
StageAccess authorisation
1 2 3
Low-noise operation access no access no access
Weather-dependent target value regulation access no access no access
Activate, deactivate program clock access access no access
Programming access no access no access
Time setting access no access no access
Test operation access no access no access
NOTE:
– For colder outside temperatures (Lo_A), the value Lo_Ti must be higher that the value Hi_Ti, as hotter
water is required.
– With warmer outside temperatures (Hi_A) the value Hi_Ti must be lower that the value Lo_Ti, as less hot
water is required.
T
t
Target water temperature
T
A
Ambient temperature (outside air)
T
Adjustment value
Fig.6-11 View of the control system with active "Weather-dependent target value
regulation"