9. Alert and Error Message
9.1. Possible Error/Alert/Troubleshooting
Sr.No.
Message
displayed.
Error Description.
Trouble shooting.
1
CRITICAL
ERROR
NV memory error.
Contact manufacturer
2
SPOOL
SENSOR
FAILED
Mechanical spool
error
Need to check pneumatic pressure and if the
pressure is OK then need to check
internal circuit.
Contact manufacturer.
3
HARDWARE
SENSOR
FAILED
feedback sensor
related error
Need to check pneumatic pressure and if the
pressure is OK then need to check
internal circuit.
Contact manufacturer.
4
CRC ERROR
NV memory error.
NV memory error.
Contact manufacturer
5
DEVICE NOT
CALIBRATED
Device not calibrated
Calibration not done. Need to calibrate.
6
DEVICE
INACTIVE
Device in Manual
mode
Manual mode.
To go to auto mode long press mode key.
7
INSUFFICIENT
SUPPLY
PRESSURE
Air Pressure related
error
Adjust pneumatic pressure
8
OVER SUPPLY
PRESSURE
Air Pressure related
error
Adjust pneumatic pressure
9
POSITION OUT
RANGE
Device not calibrated.
Feedback sensor
related error.
Calibration error. Need to
Recalibrate. If problem persists contact
manufacturer
10
FAIL SAFE
ACTIVE
Input signal 4-20 mA
not available.
Input signal
not available
11
DEVIATION
ERROR
Error in 4-20 mA input
signal/pressure/sensor
feedback
Calibration error. Need to
Recalibrate. If problem persists contact
manufacturer
12
DEADBAND
OUT RANGE
Device calibration
related error.
Calibration error, Need to recalibrate.
If problem persists check linkage between
positioned and actuator.
13
TEMPERATURE
OUT RANGE
Ambient temperature
is not within
operational
temperature range.
If ambient temperature is out of the operation
range of -20° to 85° then place the device in the
given temperature range, If the temperature is
within the said range, then ambient sensor
problem.
15
PRESSURE
OUT RANGE
Pneumatic pressure
related error
Adjust pneumatic pressure