6. Installation / Mounting:
6.1. Safety Instructions:
The equipment must be installed in the accordance with the laws, guide lines and rules
applicable within the country.
WARNING:
• ENSURE THAT SUPPLY VOLTAGE SHOULD NOT EXCEED MORE THAN > 20 % OF
RATED VOLTAGE. (FOR CURRENT AND VOLTAGE RATINGS REFER CATALOGUE)
• NO MECHANICAL REWORK ALLOWED BY CUSTOMER. MECHANICAL REWORK CAN
INCREASE CLEARANCE BETWEEN HOUSING AND COVER.
• DO NOT OPEN COVER / CABLE GLAND WHEN POSITIONER IS UNDER OPERATION
OR IN ENERGIZED CONDITION.
CAUTION:
THE CURRENT AND VOLTAGE LIMITATION HAS TO BE OBSERVED AS PER THE TAG PLATE.
THE WIRING AND CONNECTION SHOULD BE CARRIED OUT WITH PROPER GLAND AND CARE SHOULD BE
TAKEN TO AVOID WATER SEEPAGE.
CONFIRM THE AREA IS NON-HAZARDOUS BEFORE OPENING THE COVER OF THE ENCLOSURE FOR
MAKING ELECTRICAL CONNECTIONS.
THE PLUGS GIVEN ALONG WITH BOX ARE TO BE REMOVED AND METALLIC PLUG TO BE USED.
ENSURE CABLE GLAND IS PROPERLY FITTED USING SOUND ENGINEERING PRACTICE ENSURING THAT
RAIN WATER / OTHER FLUIDS DO NOT ENTER IN THE SMART POSITIONER BOX.
THE PERSON WHO OPERATES THE LIMIT SWITCH SHOULD HAVE ENOUGH KNOWLEDGE OF ELECTRICAL
ENGINEERING.
CAUTION IP67 / IP68:
ENSURE CABLE GLAND AND GASKET IS PROPERLY FITTED USING SOUND ENGINEERING PRACTICE
ENSURING THAT RAIN WATER / OTHER FLUIDS DO NOT ENTER IN THE SMART POSITIONER BOX.
TIGHTEN THE COVER BOLTS FULLY TO AVOID WATER SEEPAGE INSIDE THE SMART POSITIONER
BOX.
USE UCIL SYNCHEM MAKE GRIP SEAL CABLE JOINING COMPOUND OR EQUIVALENT TO SEAL CABLE
GLAND. FOR PRECAUTION & APPLICATION OF SEALING COMPOUND USE ORIGINAL MANUFACTURERS
OPERATIONAL MANUAL.