Fix the positioner along with the mounting bracket at the centre of the control valve
depending on the stroke of the control valve.
Insert the shaft in the slot in the scale and lock it using the locking spring as shown in fig 3.
Make sure that the scale is horizontal when calibrating the positioner.
Secure the bolts firmly and proceed for calibration.
Figure 3: Detailed view of positioner with globe valve.
Note:
Adjust the height of the positioner on the cast iron yoke until the lever is horizontal (based
on a visual check) at half stroke of the valve.