MODEL 53515/53615/63515/63615/73515/73615
10
50mm) or 1.9"OD
(Outer diameter
48.3mm)
DF softener,
time clock
type
1-1/2"D-GB
(Outer diameter
50mm) or 1.9"OD
(Outer diameter
48.3mm)
UF softener,
time clock
type
Remark: M—Male F—Female
1.5. Installation
A. Installation notice
Before installation, read all those instructions completely. Then
obtain all materials and tools needed for installation.
The installation of product, pipes and circuits should be
accomplished by professional to ensure the product can operate
normally.
Perform installation according to the relative pipeline regulations
and the specification of Water Inlet, Water Outlet, Drain Outlet, and Brine
Line Connector.
B. Device location
①The filter or softener should be located close to drain.
②Ensure the unit is installed in enough space for operating and
maintenance.
③Brine tank needs to be close to softener.
④The unit should be kept away from the heater and not be exposed to
outdoor. Sunshine or rain will cause the system damage.
⑤Please avoid installing the system in circumstance of acid/alkaline,
magnetic or strong vibration circumstance, because above factors will
cause the system disorder.
⑥Do not install the filter or softener, drain pipeline or overflow pipe in
circumstance which temperature may drop below 5℃, or above 45℃.