© 2015 SafeLine and all the SafeLine products and accessories are copyrighted by law.
MX3 v1.06 EN
Confi guration
OTHER CODES CODE DATA COMMENTS
Outputs *88* - - # The fi rst digit specifi es the output, i.e Output 1 or Output 2
The second digit specifi es the function.
0 = Pictogram (Output 1 - Yellow, Output 2 - Green)
1 = Activate with DTMF 8/9 (Output 1 - DTMF 8, Output 2 - DTMF 9)
2 = System failure
3 = Alarm
Example:
*88*11# - Output 1, Activate with DTMF 8
*88*23# - Output 2, Alarm
Alarm button type *89* - # 0 = Normally-open contact, NO (Default)
1 = Normally-closed contact, NC
Microphone sensitivity *90* - # The sensitivity of the microphone can be reduced in three levels.
0 = No reduction (förvalt värde)
1 = 20 % Reduction
2 = 40 % Reduction
3 = 60 % Reduction
Change password *91* - - - - # Change password (default=0000).
Operator silence disconnect *92* - # Disconnects the call when the alarm operator has been quiet for
longer than the time set.
0 = Off (default)
1 = 30 sec
2 = 60 sec
3 = 90 sec
Simulate an alarm event *94* - # Triggers an alarm event after confi guration is terminated.
1 = Emergency call
2 = Test alarm
3 = Battery failure
4 = Microphone/Loudspeaker failure
5 = Receipt on voice call
6 = Maintenance
7 = Main unit power failure
8 = Stuck button alarm
Reset to default settings *99* - # 1 = Factory default
2 = Default P100(The following codes will be set):
*21*0#, *22*0#, * 27*03#, *76*4#, *80*1#, *84*1#, *88*1#
3 = Default CPC(The following codes will be set):
*21*3#, *22*3#, *27*03#, **76*4#, 80*1#, *84*1#, *88*1#
4 = Default VOICE(The follo wing codes will be set):
*21*1#, *22*1#, * 27*03#, *76*4#, *80*1#, *84*1#, *88*1#