2
1.8.4
1.8.4
1.8.4
1.8.4 Speed
Speed
Speed
Speed sensor
sensor
sensor
sensor input
input
input
input
1 、 High speed digital (DC)input
— Speed sensor ( Figure 1 — 4 )
— comparator with hysteresis loop
— photoelectricity isolation
— Built in current source used for mechanical contact
— power supplied by +24V DIO
— type:
Voltage/current or contact type sensor
Apply to all SAIMO sensors
— frequency range
:
— Voltage/current type sensor : 0.25 — 2.0 kHz
— contact type sensor : 0.25 — 30 Hz
— Low threshold : +1.0 Vdc ( Min. )
— high threshold : +3.2 Vdc ( Max. )
— Low or high pulse cycle
:
— Voltage/current type sensor : 200 us ( Min. )
— Contact type sensor : 15 ms ( Min. )
— hysteresis loop : 0.5 Vdc ( Min. )
— input resistance
:
10 k Ω
(
typical
)
500 Ω ( Min. )
— input current : - 2 mA ( at 0 Vdc )
— Max. safety input voltage :
Peak value : ± 50V , continuous voltage
— cable length:1.6 km , use 18AWG shielded cable.