EasyManua.ls Logo

SAJ H2-6K-S3 - Setting Reactive Power Control (For Australia)

SAJ H2-6K-S3
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H2 Series
52
6.8 Setting Reactive Power Control
(For Australia)
6.8.1 Setup Fixed Power Factor Mode & Fixed Reactive Power Mode
Fixed Power Factor Mode
Step 1: Select Power Adjustment and enter password “201561”.
Step 2: Select Capacitive Power Factor or Inductive Power Factor according to your local grid regulation. The power factor
range is from 0.8 leading ~ 0.8 lagging.

Related product manuals