H2 Series
52
6.8 Setting Reactive Power Control
(For Australia)
6.8.1 Setup Fixed Power Factor Mode & Fixed Reactive Power Mode
Fixed Power Factor Mode
Step 1: Select Power Adjustment and enter password “201561”.
Step 2: Select Capacitive Power Factor or Inductive Power Factor according to your local grid regulation. The power factor
range is from 0.8 leading ~ 0.8 lagging.