Suntrio Plus Series
-40-
Change Password
3. Enter the new password and
click OK to save the change.
PV Mode Setting
1. In the main LCD interface,
press “ENT” button, then press
to enter into “Setting”.
2.PressandthenpressENTto
enter into “PV Mode Setting”.
Pressand to choose PV
mode.then choose to confirm.
1-- PV1,PV3,PV2 independent
2--PV1//PV2; PV3 independent
3--PV1//PV3; PV2 independent
4--PV2//PV3; PV1 independent
5-- PV1//PV2// PV3
Attention: This mode shall be
set before the inverter is
connected to the power grid, and
don’t set it when the inverter is
being connected to the grid.