EN | 39SMARTY v2023.1
8.6. CO
2
CONCENTRATION ACCORDING TO PETTENKOFER LIMIT
8.7. CONNECTION OF SUPPLY AND EXHAUST AIR DAMPERS (VERSION 1.1 / 1.2)
$OOYHUVLRQVRI6PDUW\FDQEHHTXLSSHGZLWKRXWGRRUDLUDQGH[KDXVWDLUGDPSHUV'DPSHUVDUHRSHUDWHGE\2SHQ&ORVHDFWXDWRUV
Installation diagram
See "PIPING AND INSTRUMENTATION DIAGRAM".
Wiring diagram
Automation controller D zone. Upon activation of output X13:3, the dampers open. Upon activation of output X13:4, the dampers close.
N(L1)
PE
4 3 2 1
230VAC
ON/OFF
N
L1
L1
M3
PE PE
DO4 (L(L2))
DO3 (L(L2))
230VAC
ON/OFF
N
L1
L1
M2
8.8. OUTSIDE AIR DAMPERS (VERSION S300)
2XWVLGHDLUGDPSHUVFDQEHXVHGZLWK6PDUW\SURGXFWV'DPSHUVVKRXOGEHFRQWUROOHGE\2Q2ႇRU6SULQJUHWXUQDFWXDWRUV8SRQDFWLYDWLRQRI
output Q34 (T14:1), dampers shall open. Upon deactivation of output, dampers shall close. When activated, 230V voltage is applied to Q34 output.
%\GHIDXOWGDPSHUFRQWURORXWSXWLVDOUHDG\DFWLYDWHGLQFRQ¿JXUDWLRQ
2XWVLGHDLUGDPSHUFRQWUROVLJQDO/9
2XWSXWGLJLWDOUHOD\9$&PD[$QRUPDOO\RSHQFORVHG
4
7
Figure 8.8.1. Connection for outside dampers
WARNING: High voltage on output.
8.9. CONNECTION OF REMOTE CONTROL PANEL, KNX ROOM SENSORS AND MODBUS
(VERSION S300)