EN | 51SMARTY v2023.1
10.2. HEATER
,QRUGHUWRFRQWUROHOHFWULFDOKHDWHULWKDVWREHFRQ¿JXUHGE\IROORZLQJVWHSV
•In CONFIGURATIONZLQGRZVHOHFWONLINE CONFIGURATION BASIC and press OKRQZDUQLQJ:DLWIRUWKHGHYLFHWRVZLWFKLQFRQ¿JXUDWLRQPRGH
•Set HEATING COIL parameter to ELECTRIC HEATING COIL 21Y.
• Press APPLY – RESTART DEVICEEXWWRQDQGZDLWIRUFRQ¿JXUDWLRQWREHDSSOLHG$IWHUFRQ¿UPDWLRQRIVXFFHVVIXOGHYLFHDFWLYDWLRQSUHVVDONE.
•In CONFIGURATIONZLQGRZVHOHFWONLINE CONFIGURATION EXTENDED and press OKRQZDUQLQJ:DLWIRUWKHGHYLFHWRVZLWFKLQFRQ¿JXUDWLRQPRGH
• Select Q1 as ELECTRIC HEATING COIL COMMAND, X8 as HEATING COIL OVERTEMPERATURE DETECTOR and A3 as HEATING COIL ELECTRIC POSITION.
• Press APPLY – RESTART DEVICEEXWWRQDQGZDLWIRUFRQ¿JXUDWLRQWREHDSSOLHG$IWHUFRQ¿UPDWLRQRIVXFFHVVIXOGHYLFHDFWLYDWLRQSUHVVDONE.
10.3. PREHEATER
,QRUGHUWRFRQWUROHOHFWULFDOSUHKHDWHUZKLFKKDVEHHQFRQQHFWHGDVUHTXLUHGLQVHFWLRQ"8.1.3.2. PREHEATER"LWKDVWREHFRQ¿JXUHGE\IRO-
ORZLQJVWHSV
•In CONFIGURATIONZLQGRZVHOHFWONLINE CONFIGURATION BASIC and press OKRQZDUQLQJ:DLWIRUWKHGHYLFHWRVZLWFKLQFRQ¿JXUDWLRQPRGH
•Set PREHEATING COIL parameter to ELECTRIC PREHEATING COIL 21Y.
• Press APPLY – RESTART DEVICEEXWWRQDQGZDLWIRUFRQ¿JXUDWLRQWREHDSSOLHG$IWHUFRQ¿UPDWLRQRIVXFFHVVIXOGHYLFHDFWLYDWLRQSUHVVDONE.
•In CONFIGURATIONZLQGRZVHOHFWONLINE CONFIGURATION EXTENDED and press OKRQZDUQLQJ:DLWIRUWKHGHYLFHWRVZLWFKLQFRQ¿JXUDWLRQPRGH
• Select Q1 as ELECTRIC PREHEATING COIL COMMAND, X8 as SUPPLY AIR TEMP. AFTER PREHEATING COIL, B1 as OUTSIDE AIR TEMPERATURE, A3 as
PREHEATING COIL ELECTRIC POSITION and X3 as PREHEATING COIL OVERTEMPERATURE DETECTOR.
• Press APPLY – RESTART DEVICEEXWWRQDQGZDLWIRUFRQ¿JXUDWLRQWREHDSSOLHG$IWHUFRQ¿UPDWLRQRIVXFFHVVIXOGHYLFHDFWLYDWLRQSUHVVDONE.
10.4. SMOKE DETECTOR
%\GHIDXOWVPRNHGHWHFWRULQSXWLVDFWLYDWHGDQGFRQ¿JXUHGDVNOLQSXW,QRUGHUWRXVHD1&VZLWFKLQSXWPXVWEHUHFRQ¿JXUHGWR1&E\IROORZLQJ
steps:
•In CONFIGURATIONZLQGRZVHOHFWONLINE CONFIGURATION EXTENDED and press OKRQZDUQLQJ:DLWIRUWKHGHYLFHWRVZLWFKLQFRQ¿JXUDWLRQPRGH
• Select D1 as SMOKE EXTRACTION NORMALLY CLOSED.
10.5. FIREPLACE PROTECTION, SYSTEM MODE SWITCH OR RAPID VENTILATION SWITCH INPUT
,QRUGHUWRFRQ¿JXUH'LQSXWDV)LUHSODFHSURWHFWLRQ
•In CONFIGURATIONZLQGRZVHOHFWONLINE CONFIGURATION EXTENDED and press OKRQZDUQLQJ:DLWIRUWKHGHYLFHWRVZLWFKLQFRQ¿JXUDWLRQPRGH
• Select D2 as FIREPLACE VENTILATION INPUT.
6\VWHPPRGHVZLWFKIXQFWLRQFDQEHXVHGWRHQDEOHRQHSUHVHOHFWHGV\VWHPPRGH6\VWHPPRGHIRUWKLVVZLWFKFDQEHVHWE\IROORZLQJVWHSV
•In CONFIGURATIONZLQGRZVHOHFWONLINE CONFIGURATION EXTENDED and press OKRQZDUQLQJ:DLWIRUWKHGHYLFHWRVZLWFKLQFRQ¿JXUDWLRQPRGH
• Select D2 as one of the selections available:
1. INPUT ROOM OPERATING MODE COMFORT;
2. INPUT ROOM OPERATING MODE ECONOMY;
3. INPUT ROOM OPERATING MODE UNOCCUPIED;
4. INPUT ROOM OPERATING MODE PROTECTION.
5DSLGYHQWLODWLRQVZLWFKIXQFWLRQFDQEHXVHGWRERRVWIDQVSHHG,QRUGHUWRFRQ¿JXUH'LQSXWDV5DSLGYHQWLODWLRQVZLWFK
•In CONFIGURATIONZLQGRZVHOHFWONLINE CONFIGURATION EXTENDED and press OKRQZDUQLQJ:DLWIRUWKHGHYLFHWRVZLWFKLQFRQ¿JXUDWLRQPRGH
• Select D2 as RAPID VENTILATION INPUT.
After D2LQSXWLVFRQ¿JXUHGSUHVVAPPLY – RESTART DEVICEEXWWRQDQGZDLWIRUFRQ¿JXUDWLRQWREHDSSOLHG$IWHUFRQ¿UPDWLRQRIVXFFHVVIXOGHYLFH
activation press DONE.