EasyManua.ls Logo

samlexsolar SCC-30AB - PV Array Connection; DIP Switch Configuration; Battery Connection Procedure

samlexsolar SCC-30AB
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
6
INSTALLATION & OPERATION
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm 25 mm
25 mm
6 mm
6 mm
6 mm
6 mm
190 mm
108 mm
- Cut the wall / panel along the dotted line
with a jig saw.
- This will create a pocket in the wall / panel
for ush mounting of Charge Controller SCC-30AB.
Outline of the front panel
Fig. 6.1. Drawing for making the cut-out in the wall / panel
2. Make sure the PV currents will not exceed the ratings of the SCC-30AB.
3. The connections to the SCC-30AB terminals are shown in the drawing at Fig. 5.2.
A barrier type of Terminal Strip has been provided for connecting the PV array and
the battery. M-4 screws with clamping washers are used to make the connection. A
at or a #2 Philips head screw driver may be used to tighten these screws. Tighten
each terminal clamping screw to 20 inch-pounds of torque. The distance between the
barriers is 9 mm and a standard Spade Type of terminal lug meant for # 8 Stud and
AWG #10 – AWG #12 wire may be used at the end of the wires to be connected to
these terminals. 4 such terminal lugs are provided with the unit for ease of installation
4. Set the DIP Switch 1 for the voltage system, set the DIP Switch 2, 3, 4 for battery
charging algorithm.
5. Connect the BATTERY rst. Be careful that bare wires do not touch the metal case
of the controller.
The BATTERY must be connected before the Solar Panel (Module)/Array to
properly start the microcontroller, activate protections & guide installation.
A battery below 9 volts may not start the microcontroller properly. Make sure the
battery is charged before installing the system.

Table of Contents