Caution!
The erroneous connection of a voltage
source of just around 7 V (or around 2 V
when connected to the wrong pole) can
damage the positioner.
In general, it is not necessary to connect the
positioner to a bonding conductor. Should
this be required, however, this conductor
can be connected inside the device.
For operation of the limit switches in Type
3730-11/-13/-18 Positioners, switching
amplifiers which comply with
EN 60947-5-6 must be connected to termi-
nals 41/42 and 51/52 in the output circuit.
If the positioner is to be installed in hazard-
ous areas, the relevant regulations must be
observed.
Refer to Fig. 10 for the terminal assignment.
Note!
The minimum permissible reference variable
should not fall below 3.7 mA.
Accessories:
Plastic cable gland M20x1.5:
Black Order no. 8808-1011
Blue Order no. 8808-1012
Nickel-plated brass Order no. 1890-4875
Adapter M20 x 1.5 to ½ NPT
Aluminum, powder-coated
Order no. 0310-2149
EB 8384-1 EN 27
Connections
Fig. 10 · Electrical connections
+11 -12 +51 -52 +41 -42
(A2) (A1)
mA control signal
Explosion-protected version
Connection for
switching amplifiers acc. to EN 60947-5-6
Version without explosion protection
Connection to
PLC binary input acc. to EN 61131
Limit switches