Troubleshooting
4-6 Samsung Electronics
Option item SEG1 SEG2 SEG3 SEG4 Function
Target low pressure cali-
bration for cooling ³⁾
0 9
0 0
Initial set pressure for cooling
(Factory default)
0 1 -2.84 psi
0 2 -5.69 psi
0 3 -8.53 psi
0 4 -11.38 psi
0 5 -14.22 psi
0 6 +2.84 psi
0 7 +5.69 psi
0 8 +8.53 psi
0 9 +11.38 psi
1 0 +14.22 psi
Target high pressure
calibration for heating ⁴⁾
1 0
0 0
Initial set pressure for heating
(Factory default)
0 1 +2.84 psi
0 2 +5.69 psi
0 3 +8.53 psi
0 4 +11.38 psi
0 5 +14.22 psi
0 6 -2.84 psi
0 7 -5.69 psi
0 8 -8.53 psi
0 9 -11.38 psi
1 0 -14.22 psi
¹⁾ Current restriction rate : When restriction option is set, cooling and heating performance may decrease.
²⁾ Set this value only when the diameter of the installed gas piping is smaller than the standard piping diameter.
Do NOT use it for performance enhancement purposes.
³⁾ Target low pressure for cooling can be set in a range of 113.79–170.68 psi.
⁴⁾ Target high pressure for heating can be set in a range of 284.47–526.26 psi.
Test operation mode and check mode (Cont.)