Troubleshooting
Samsung Electronics 4-5
Test operation mode and check mode (Cont.)
Option item SEG1 SEG2 SEG3 SEG4 Function
Channel address 0 0
A U Automatic setting (Factory default)
00~15 Manual setting
Snow accumulation
prevention control
0 1
0 0 Disabled (Factory default)
0 1 Enabled
Step for Silence mode 0 2
0 0 Disabled (Factory default)
0 1 Step1
0 2 Step2
0 3 Step3
Type of Silence mode 0 3
0 0
Automatic Silence mode (Factory
default)
0 1 Manual Silence mode
Temperature unit 0 4
0 0 Celsius
0 1 Fahrenheit(default)
Current restriction
rate ¹⁾
0 6
0 0
100%
(Factory
default)
0 1 95%
0 2 90%
0 3 85%
0 4 80%
0 5 75%
0 6 70%
0 7 65%
0 8 60%
0 9 55%
1 0 50%
1 1 100%
Dedicated mode for
cooling/ heating
0 7
0 0 Cooling / Heating operation (default)
0 1 Cooling operation only
0 2 Heating operation only
Long-piping pressure
calibration ²⁾
0 8
0 0
Within
98.4 ft (30 m)
(Factory default)
0 1
98.4 ~ 164.0 ft
(30 ~ 50 m)
(Cooling:-9.96psi,
Heating:+4.27psi)