EasyManuals Logo

Samsung AC100RN4PKG User Manual

Samsung AC100RN4PKG
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #192 background imageLoading...
Page #192 background image
Troubleshooting
4-36 Samsung Electronics
4-3-12 Reverse phase / Loss phase detection (3-phase outdoor unit) (Error Code : E425 )
1. When power is on, it checks the power status used for 3-phase power compressor.
When the order of 3-phase L1(R) – L2(S) – L3(T) is changed (Reverse phase) or there is a phase that does not supply power (Loss phase), it
will display
and the air conditioner will stop operating.
1) Check the voltage on L1(R) – L2(S) phase/ L1(R) – L3(T) phase/ L2(S)
– L3(T) phase.
2) When there is any terminal that does not have normal voltage,
check the external power of the air conditioner and take
appropriate measures.
3) If 3-phase power is normal check the phase of the power wire using
3-phasetester. If it shows reverse phase, change the current power
wire connection.
4) After completing above, press reset key (K3) then check the power
again.
3-phase tester

Table of Contents

Other manuals for Samsung AC100RN4PKG

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AC100RN4PKG and is the answer not in the manual?

Samsung AC100RN4PKG Specifications

General IconGeneral
BrandSamsung
ModelAC100RN4PKG
CategoryAir Conditioner
LanguageEnglish

Related product manuals