Installation Procedure
02 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 -
External room
temperature sensor /
Minimizing fan operation
when thermostat is off
Central control -
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 Use of drain pump - -
EEV Step when
heating stops
Dew removal operation
in Wind-Free mode /
Evaporator Drying fan
mode / Auto fan smart
comfortable mode
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
Setting the output of
external control / External
heater signal / Cooling
operation signal / Free
Cooling control signal
- Buzzer
Number of hours using
filter
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3
Individual control
of a remote control
Heating setting
compensation / Removing
condensated water in
heating mode
EEV Step of stopped unit
during oil return/defrost
mode
- -
When setting the option other than above SEG values, the option will be set as “0”.
SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central
control option as 0 (Disuse) to exclude the indoor unit from the central control.
The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2 (1000
hours).
If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set
to 0 (Indoor 1).
After disassembling the cover
panel, you can connect the
wires from the indoor unit's
display to the wired remote
control and MIM-B14.
Be sure to connect the wired
remote control for installation
after cutting the COM2 wire.
4 PIN : Error check
(MIM-B14)
2 PIN : External ON/OFF
Control(MIM-B14)
COM2(F3, F4) :
F3/F4
DB68-08953A-00_IM_DVM QMD_EU_EN_.indd 21 2020-02-10 오후 4:23:11