21
Installation Procedure
02 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 -
External room
temperature sensor /
Minimizing fan operation
when thermostat is off
Central control -
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 Use of drain pump - -
EEV Step when
heating stops
Dew removal operation
in Wind-Free mode /
Evaporator Drying fan
mode / Auto fan smart
comfortable mode
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
Setting the output of
external control / External
heater signal / Cooling
operation signal / Free
Cooling control signal
- Buzzer
Number of hours using
filter
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3
Individual control
of a remote control
Heating setting
compensation / Removing
condensated water in
heating mode
EEV Step of stopped unit
during oil return/defrost
mode
- -
• When setting the option other than above SEG values, the option will be set as “0”.
• SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
• However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central
control option as 0 (Disuse) to exclude the indoor unit from the central control.
• The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
• If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2 (1000
hours).
• If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set
to 0 (Indoor 1).
After disassembling the cover
panel, you can connect the
wires from the indoor unit's
display to the wired remote
control and MIM-B14.
Be sure to connect the wired
remote control for installation
after cutting the COM2 wire.
4 PIN : Error check
(MIM-B14)
2 PIN : External ON/OFF
Control(MIM-B14)
COM2(F3, F4) :
F3/F4
DB68-08953A-00_IM_DVM QMD_EU_EN_.indd 21 2020-02-10 오후 4:23:11