20
Installation Procedure
Installation Procedure
Setting an indoor unit address (MAIN/RMC)
1 Check whether power is supplied or not.
‐ When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2 Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
3 Assign an indoor unit address by wireless remote control.
The initial setting status of indoor unit ADDRESS(MAIN/RMC) is “0A0000-100000-200000-300000”.
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE Mode Setting Main address
100-digit of indoor
unit address
10-digit of indoor
unit
The unit digit of an
indoor unit
Indication
and Details
Indication DetailsI Indication Details Indication Details Indication Details Indication Details Indication Details
0 A
0 No Main address
0~9 100-digit 0~9 10-digit 0~9
A unit
digit
1
Main address
setting mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
-
Setting RMC address
-
Group channel (*16) Group address
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0 No RMC address
RMC1 0~F RMC2 0~F
1
RMC address
setting mode
CAUTION
• When A~F is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
• If you set the SEG3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option value of
SEG5~6.
• If you set the SEG9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value of
SEG11~12.
• You cannot set SEG11 and SEG12 as F value at the same time.
Setting an indoor unit installation option (suitable for the condition of each installation location)
1 Check whether power is supplied or not.
‐ When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2 Set the installation option according to the installation condition of an air conditioner.
‐ The default setting of an indoor unit installation option is 020010-100000- 200000-300000.
‐ Individual control of a remote control(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
3 Set the indoor unit option by wireless remote control.
DB68-08953A-00_IM_DVM QMD_EU_EN_.indd 20 2020-02-10 오후 4:23:11