20
Installation Procedure
English
Installation Procedure
Setting an indoor unit address (MAIN/RMC)
1 Check whether power is supplied or not.
When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2 Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
3 Assign an indoor unit address by wireless remote control.
The initial setting status of indoor unit ADDRESS(MAIN/RMC) is “0A0000-100000-200000-300000”.
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE Mode Setting Main address
100-digit of indoor
unit address
10-digit of indoor
unit
The unit digit of an
indoor unit
Indication
and Details
Indication DetailsI Indication Details Indication Details Indication Details Indication Details Indication Details
0 A
0 No Main address
0~9 100-digit 0~9 10-digit 0~9
A unit
digit
1
Main address
setting mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
-
Setting RMC address
-
Group channel (*16) Group address
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0 No RMC address
RMC1 0~F RMC2 0~F
1
RMC address
setting mode
CAUTION
When A~F is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
If you set the SEG3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option value of
SEG5~6.
If you set the SEG9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value of
SEG11~12.
You cannot set SEG11 and SEG12 as F value at the same time.
Setting an indoor unit installation option (suitable for the condition of each installation location)
1 Check whether power is supplied or not.
When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2 Set the installation option according to the installation condition of an air conditioner.
The default setting of an indoor unit installation option is 020010-100000- 200000-300000.
Individual control of a remote control(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
3 Set the indoor unit option by wireless remote control.
DB68-08953A-00_IM_DVM QMD_EU_EN_.indd 20 2020-02-10 오후 4:23:11