Installation Procedure
Installation Procedure
05 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 5
Use of Auto Change
Over for HR only in
Auto mode / Use of
Cooling only indoor
unit of HR
(When setting SEG3)
Standard heating
temp. Offset
(When setting SEG3)
Standard cooling
temp. Offset
(When setting SEG3)
Standard for mode
change Heating →
Cooling
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1
(When setting SEG3)
Standard for mode
change Cooling →
Heating
(When setting SEG3)
Time required for
mode change
Compensation option
for Long pipe or
height difference
between indoor units
MTFC -
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 - - - -
Control variables when
using hot water /
external heater (*4)
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3 - - -
Forced FAN
Operation for
Heating and Cooling
-
05 series installation option (Detailed)
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
Use of Auto Change Over for HR only
in Auto mode / Use of Cooling only
indoor unit of HR
(When setting SEG3)
Standard heating
temp. Offset
(When setting
SEG3) Standard
cooling temp.
Offset
(When setting SEG3)
Standard for mode
change Heating →
Cooling
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 5
0 Follow product option
0 0 °C 0 0 °C 0 1 °C
1 0.5 °C 1 0.5 °C 1 1.5 °C
1
Use Auto Change Over for
HR only
2 1 °C 2 1 °C 2 2 °C
3 1.5 °C 3 1.5 °C 3 2.5 °C
4 2 °C 4 2 °C 4 3 °C
2
Use Cooling only indoor
unit for HR
5 2.5 °C 5 2.5 °C 5 3.5 °C
6 3 °C 6 3 °C 6 4 °C
7 3.5 °C 7 3.5 °C 7 4.5 °C