27
Installation Procedure
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
(When setting SEG3)
Standard for mode change
Cooling → Heating
(When setting SEG3)
Time required for mode
change
Compensation option for
Long pipe or height difference
between indoor units
MTFC (*3)
-
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details
1
0 1 °C 0 5min 0 Default
0 Default
1 1.5 °C 1 7min
1
(*1) Height difference
is more than 30m
or (*2) Distance is
longer than 110m
2 2 °C 2 9min
3 2.5 °C 3 11min
4 3 °C 4 13min
2
(*1) Height difference
is 15~30m or (*2)
Distance is 50~110m
2 Use
5 3.5 °C 5 15min
6 4 °C 6 20min
7 4.5 °C 7 30min
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation -
- - - -
Control variables when using hot water / external heater (*4)
Indication
and Details
Indication Details
Indication
Details
2
Set temp. for heater On/Off Delay time for heater On
0 At the same time as thermo on No delay
1 At the same time as thermo on 10 minutes
2 At the same time as thermo on 20 minutes
3 1.5 °C No delay
4 1.5 °C 10 minutes
5 1.5 °C 20 minutes
6 3.0 °C No delay
7 3.0 °C 10 minutes
8 3.0 °C 20 minutes
9 4.5 °C No delay
A 4.5 °C 10 minutes
B 4.5 °C 20 minutes
C 6.0 °C No delay
D 6.0 °C 10 minutes
E 6.0 °C 20 minutes
DB68-08953A-00_IM_DVM QMD_EU_EN_.indd 27 2020-02-10 오후 4:23:12