EasyManua.ls Logo

Samsung AM072FXVAFH series - Compressor Discharge or Top Temperature Sensor Breakaway Error

Samsung AM072FXVAFH series
293 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-55
4-4-21 Compressor Discharge or Top temperature sensor breakaway error
Outdoor unit display
(Compressor 1 Discharge) (Compressor 2 Discharge)
(Compressor 1 Top) (Compressor 2 Top)
Indoorunit display
Judgment Method
1) Faulty compressor frequency of 60Hz or higher.
2) Suction temperature > Low pressure saturation temperature +10
3) Relevant discharge or Top temperature < High pressure saturation temperature
4) In case of
keep 30 minutes in state that satisfy all above conditions (1,2&3) for 30min.
Cause of problem
 Compressor discharge or Top temperature sensor breakaway and defective / Ineffective start of compressor
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation
Defrost TimerFan Filter/MPI
Operation
Defrost Timer Filter
Operation
TimerTurbo
24 27
××
×
◑◑◑× ×◑◑◑
:
ON
:
Flash
×:
OFF
1.
Cause of problem
Replace the PCB
Re-insert sensor Re-attach sensor holder
No
Yes
Is the Discharge
or Top temperature sensor and the sensor holder
correctly attached?
Defective sensor : Replace sensor
No
Yes
Is the Discharge or Top temperature
sensor resistance value reasonable?
(Refer to the “Note 1”)
NOTE1
TOP1 : CN43 (3, 4)
TOP2 : CN45 (5, 6)
DIS1 : CN43 (1, 2)
DIS2 : CN45 (3, 4)
Resistance value
measure part
Resistance value
measure part
TOP1 TOP2
Temperature(°C) Resistance(K)
130
120
100
80
60
25
20
10
0
8.9
11.2
18.5
32.0
59.0
200.0
242.0
362.0
553.0

Table of Contents