Troubleshooting
Samsung Electronics 4-115
1.
How to check
4-4-55 Option setting error of outdoor unit
(Operation) ×(Reservation) (Blast) ×(Filter) ×(Defrost)
t0QUJPOTFUUJOHFSSPSPGPVUEPPSVOJU
(There is No Compressor start in a Unit because of Compressor Cut off Option Setting. )
t3FGFSUPUIFKVEHNFOUNFUIPECFMPX
Indoor Unit Display
Judgment Method
Special Cause
Outdoor Unit Display
Download relevant model EEPROM and then reset.
※ Execute automatic commissioning for UP
cancellation after EEPROM download.
Set the compressor breakdown setting
value as "not set"
※ When There is No Compressor start in a Unit
because of Compressor Cut off Option
Setting, E560.
No
Yes
Is the Compressor breakdown
setting value is "not set"?
Connect outdoor unit EEPROM and then reset.
No
Yes
Is the outdoor unit EEPROM accurately
connected to connector?