Samsung Electronics 8-1
8. Key Options
8-1 Outdoor unit option switch settings
Switch SettingSetting Remarks
SW51/
SW52
Setting total number of installed indoor unit SW51:
Tens digit, SW52: Units digit
Setting can be done from the main outdoor unit only (sub
unit: setting is nnecessary)
Ex) When 12 indoor units ar
e installed SW51: 1, SW52: 2
SW53
K6
ON
Enable maximum capacity restriction for cooling
operation
Restrict excessive capacity increase when operating indoor
units with small capacity
OFF
Disable maximum
capacity restriction for cooling
operation
-
K7 K8 Selecting outdoor unit address
ON ON Outdoor unit address: No 1 Main unit
ON OFF Outdoor unit address: No 2 Sub unit 1
OFF ON Outdoor unit address: No 3 Sub unit 2
OFF OFF Outdoor unit address: No 4 Sub unit 3
SW57 Setting total number of connec
ted MCU
Setting can be done from Main unit only.
Ex) When 3 MCUs are installed SW57: 3,
When 10 MCUs are installed SW57: A
AM6666XV666
rX rY rZ r[
MCU
< A TYPE >