3-62 Samsung Electronics
STEP
Occasion that compressor is 1 inside outdoor unit
1 -
2-
3 Lock all SVC valve of liquid pipe and gas pipe.
4 Enter in vacuum mode and establish as all EEV and Valve open.
5
Reclaim refrigerant of outdoor unit using Recovery Unit.
Ǒ
When there is no Recovery Unit, refer to below contents.
1.
If refrigerant release driving is enforced, refrigerant remaining amount of outdoor unit inside
is about 0.5kg ordinarily. Temperature can remain more refrigerant because refrigerant lls to
Accumulator in the winter day.
2.
Refer to factory charging refrigerant had registered to Label of outdoor unit.
3.
Can get help that decide an addition refrigerant quantity if use refrigerant quantity decision
function that use S-Checker.
6
Turn o the power linked by outdoor unit.
7
Separate compressor that broke down from outdoor unit.
Conrm through manifold gauge whether refrigerant of outdoor unit was reclaimed all
necessarily before use welding machine for replace of compressor.
8
Measure quantity of broke down oil of compressor.
9
Conrm state and color of compressor oil that broke down.
10
-
11
Decide quantity of oil to pour in addition according to sheep of changing oil of compressors.
12
Change by new compressor.
Add oil according to sheep of oil that pour decided addition before.
13
Establish again by vacuum mode after connect power.
14
Execute leakage examination using nitrogen
ĺ
vacuum work
15
Add a refrigerant quantity deciding from step 5.
16
Execute Auto Trial Operation after open SVC Valve.
AM038/048/055KXWD
✳✳
3-3 Caution at compressor exchange
غ
Compressor exchange order