Troubleshooting
4-60 Samsung Electronics
1. High pressure sensor Open / Short error determination method
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open / Short error will occur if the input voltage standard range of 0.5V~4.95V is exceeded
2. How to ch
eck
Replace high pressure sensor
Restart after connecting the connector to the PCB
No
Yes
Did the high pressure sensor connector
breakaway from the PCB?
Charge the refrigerant after vacuum
No
Yes
Is there refrigerant inside the set?
(Please check by connecting the manifold gauge to
the service valve)
Replace PCB
No
Yes
Out of the PCB high pressure sensor terminals, is
there voltage between pins (3 and 4) 5V?
The ف mark is the 1st pin on the PCB.
غ AM038/048/055KXWD
✳✳
High pressure sensor error (Open / Short)
(cont.)
Outdoor unit display
Indoorunit display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation
Defrost TimerFan Filter/MPI
Operation
Defrost Timer Filter
18℃ 21℃
Turbo
24℃ 27℃
◑××◑×◑×◑×◑××◑◑
※ ● :
ON
◑ :
Flash
×:
OFF
Judgment Method
Refer to the how to check below.
Cause of problem
Disconnection or breakdown of relevant sensor.