Troubleshooting
4-58 Samsung Electronics
1.
How to check
Complete
Is suction sensor and sensor
holder accurately attached?
Is suction sensor resistance
value reasonable?
(Refer to E231)
Replace the defective sensor
No
Re-insert the sensor.
Reassemble the sensor holder.
No
Yes
Yes
غ AM038/048/055KXWD
✳✳
: Suction Temperature sensor breakaway error (cont.)
Outdoor unit display
Indoorunit display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation
Defrost TimerFan Filter/MPI
Operation
Defrost Timer Filter
18℃ 21℃
Turbo
24℃ 27℃
××◑◑◑
×
◑◑◑× ×◑◑◑
※ ● :
ON
◑ :
Flash
×:
OFF
Judgment Method
Difference of suction temperature of compressor starting verge and suction temperature that is on present operation :
When less than 2
℃ for 30 minutes to keep. (Judgment at heating operation only)
Cause of problem
Suction temperature sensor breakaway / defective