EasyManua.ls Logo

Samsung AM072FXVAFH series - Page 26

Samsung AM072FXVAFH series
293 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Specications
2-23 Samsung Electronics
Outdoor Unit(Continue)
TYPE DVM S Water 460V
Model Name(Samsung Model) AM072HXWAJR/AA AM096HXWAJR/AA AM120HXWAJR/AA AM192HXWAJR/AA
Mode -HRHRHRHR
Power Supply Φ, V, Hz ,460V,60Hz
Performance
Ton Ton 6 8 10 16
Capacity
(Nominal)
Cooling Btu/h 72,000 96,000 120,000 192,000
Heating 81,000 108,000 135,000 216,000
Capacity
(Rated)
Cooling Btu/h 69,000 92,000 114,000 184,000
Heating 77,000 103,000 129,000 206,000
Eciency
Ratings
EER Btu/W*h 20.20 19.90 15.40 11.60
IEER Btu/W*h 30.10 28.60 25.30 18.30
COP W/W 6.00 5.90 4.80 4.30
SCHE Btu/W*h 26.50 27.40 20.30 20.20
Power
MCA A 10.0 11.0 15.6 26.2
MOP
15 15 25 35
Compressor
Type - SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 2
Output kW × n 4.96 4.96 6.13 4.96 x 2
Oil
Type - PVE PVE PVE PVE
Initial Charge Liter 3.9 3.9 3.9 6.2
Condenser
Type - Plate Heat Exchanger Plate Heat Exchanger Plate Heat Exchanger Plate Heat Exchanger
Pipe Size(Female Thread) Φ, inch 1-1/4 FPT 1-1/4 FPT 1-1/4 FPT 1-1/4 FPT
Lost Head kPa (ftAq) 22(7.3) 30(10.0) 43(14.4) 54(18.1)
Water Flow Rate LPM(GPM) 80(21.1) 96(25.4) 114(30.1) 190(50.2)
Water Max. Pressure Mpa(Psi) 1.96(285) 1.96(285) 1.96(285) 1.96(285)
Piping
Connections
Liquid Pipe
Φ, mm----
Φ, inch 3/8 3/8 1/2 5/8
Gas Pipe
Φ, mm----
Φ, inch 3/4 7/8 1-1/8 1-1/8
Discharge Gas Pipe
Φ, mm----
Φ, inch 5/8 3/4 3/4 1-1/8
Installation
Limitation
Max. Length m (ft) 170(558) 170(558) 170(558) 170(558)
Max. Height m (ft) 50(164) 50(164) 50(164) 50(164)
Refrigerant
Type - R410A R410A R410A R410A
Factory Charging kg (lbs) 5.5(12.1) 5.8(12.8) 6(13.2) 9.8(21.6)
Sound
Sound Pressure dB(A) 48 48 50 51
Sound Power 70 70 70 73
External
Dimension
Net Weight kg (lbs) 167(368) 167(368) 167(368) 247(545)
Shipping Weight kg (lbs) 174(384) 174(384) 174(384) 257(567)
Net Dimensions (WxHxD)
mm 790x1000x545 790x1000x545 790x1000x545 1120x1000x545
Inch 31.1x39.4x21.5 31.1x39.4x21.5 31.1x39.4x21.5 44.1x39.4x21.5
Shipping Dimensions (Wx-
HxD)
mm 840x1200x620 840x1200x620 840x1200x620 1170x1200x620
Inch 33.1x47.2x24.4 33.1x47.2x24.4 33.1x47.2x24.4 46.1x47.2x24.4
Operating
Temp. Range(Water)
Cooling
ఁሥ
10~45(50~113) 10~45(50~113) 10~45(50~113) 10~45(50~113)
Heating
ఁሥ
10~45(50~113) 10~45(50~113) 10~45(50~113) 10~45(50~113)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 80.6 DB/66.2 WB, outdoor 95 DB, length 50m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 68 DB, outdoor 44.6 DB, length 50m of piping, fall 0ft standard.
2. If proper form heating capacity is outdoor temperature 44.6 standard and outdoor temperature goes down by below zero,
heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 656ft (Equivalent length 722ft).
5. If the indoor unit is below, height length allows up to 361ft (If over 164ft, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 131ft.

Table of Contents