Samsung Electronics 8-7
How to set the key function of the outdoor unit (cont.)
AM6666XV666
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency operation for
compressor malfunction
Individual0 0
0 0 Disabled (Factory default)
E560 will occur when all the
compressors are set as malfunction
state.
01
Set compressor 1 as malfunction
state
0 2
Set
compressor 2 as malfunction
state
Capacity correction for
cooling
Main 0 1
00
7-9 (Factory default in case
of A type PBA)
Targeted evaporation
temperature[°C]
(When low temperature value is set,
discha
rged air temperature of the
indoor unit will decrease)
01
5-7 (Factory default in case of
B type PBA)
0 2 9-11
0 3 10-12
0 4 11-13
05 12-14
06 13-15
Capcity correction for
heating
Main 0 2
00 3.0 (Factory default)
Targeted hig
h pressure [MPa]
(When low pressure value is set,
discharged air temperature
of the indoor unit will decrease)
01 2.5
0 22.6
0 32.7
04 2.8
05 2.9
06 3.1
07 3.2
08 3.3
Current restriction rate Individual0 3
0 0 100% (Factory de
fault)
When restriction option is set,
cooling and heating performance
may decrea
0 1 95 %
0 2 90 %
0 3 85 %
0 4 80 %
0 5 75 %
0 6 70 %
0 7 65 %
0 8 60 %
0 9 55 %
0 0 50 %
0 1 No restriction
Oil collection intervalMain 0 4
00 Factory default
01 Shorten the interval by 1/2
Temperature to trigge
r
defrost operation
Main 0 5
00 Factory default
01
Apply setting when the product is
being installed in humid area
such as near river or lake
Fan speed correction for
outdoor unit
Individual0 6
00 Factory default
01 Increase fan speed
Increase the outdoor unit’s fan
speed to maximum value
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)
Enable silent mode for night-time
(It operates automatically
depending on the temperature.)
Howev
er, if the external contact
interface module (MIM-B14)
is used, entering the silent mode is
available with contact signal.
0 1 LEVEL 1 / Auto
0 2 LEVEL 2 / Auto
0 3 LEVEL 3 / Auto
0 4 LEVEL 1 / External contact
0 5 LEVEL 2 / External contact
0 6 LEVEL 3 / Externa
l contact
High-head
condition setting
Main 0 8
0 0 Disabled (Factory default)
01
Level 1 of height difference type 1
(indoor unit is lower than
outdoor unit)
When outdoor unit is located
40~80m above the indoor unit
0 2
Level 2 of hei
ght difference type 1
(indoor unit is lower than
outdoor unit)
When outdoor unit is located over
80m above the indoor unit
0 3
Height difference type 2
(Outdoor unit is lower than
outdoor unit)
When indoor unit is over 30m
above the outdoor unit