Key Options
Samsung Electronics 8-7
How to set the key function of the outdoor unit (cont.)
䒲 AM6666XV666
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency operation for
compressor malfunction
Individual0 0
0 0 Disabled (Factory default)
E560 will occur when all the
compressors are set as malfunction
state.
01
Set compressor 1 as malfunction
state
0 2
Set
compressor 2 as malfunction
state
Capacity correction for
cooling
Main 0 1
00
7-9 (Factory default in case
of A type PBA)
Targeted evaporation
temperature[°C]
(When low temperature value is set,
discha
rged air temperature of the
indoor unit will decrease)
01
5-7 (Factory default in case of
B type PBA)
0 2 9-11
0 3 10-12
0 4 11-13
05 12-14
06 13-15
Capcity correction for
heating
Main 0 2
00 3.0 (Factory default)
Targeted hig
h pressure [MPa]
(When low pressure value is set,
discharged air temperature
of the indoor unit will decrease)
01 2.5
0 22.6
0 32.7
04 2.8
05 2.9
06 3.1
07 3.2
08 3.3
Current restriction rate Individual0 3
0 0 100% (Factory de
fault)
When restriction option is set,
cooling and heating performance
may decrea
0 1 95 %
0 2 90 %
0 3 85 %
0 4 80 %
0 5 75 %
0 6 70 %
0 7 65 %
0 8 60 %
0 9 55 %
0 0 50 %
0 1 No restriction
Oil collection intervalMain 0 4
00 Factory default
01 Shorten the interval by 1/2
Temperature to trigge
r
defrost operation
Main 0 5
00 Factory default
01
Apply setting when the product is
being installed in humid area
such as near river or lake
Fan speed correction for
outdoor unit
Individual0 6
00 Factory default
01 Increase fan speed
Increase the outdoor unit’s fan
speed to maximum value
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)
Enable silent mode for night-time
(It operates automatically
depending on the temperature.)
Howev
er, if the external contact
interface module (MIM-B14)
is used, entering the silent mode is
available with contact signal.
0 1 LEVEL 1 / Auto
0 2 LEVEL 2 / Auto
0 3 LEVEL 3 / Auto
0 4 LEVEL 1 / External contact
0 5 LEVEL 2 / External contact
0 6 LEVEL 3 / Externa
l contact
High-head
condition setting
Main 0 8
0 0 Disabled (Factory default)
01
Level 1 of height difference type 1
(indoor unit is lower than
outdoor unit)
When outdoor unit is located
40~80m above the indoor unit
0 2
Level 2 of hei
ght difference type 1
(indoor unit is lower than
outdoor unit)
When outdoor unit is located over
80m above the indoor unit
0 3
Height difference type 2
(Outdoor unit is lower than
outdoor unit)
When indoor unit is over 30m
above the outdoor unit