8-14 Samsung Electronics
K3 (Number of press) KEY operation Display on segment
1 time Intialize (Reset) settingSame as initial state
K4
(Number of press)
KEY operation
Display on segment
SEG 1 SEG2, 3, 4
1 time Outdoor unit model1
AM120FXW6 → Off, 1, 2
2 timesTarget frequency (Compressor 1) 2
120 Hz → 1, 2, 0
3 timesTarget frequency (Compressor 2) 3
120 Hz → 1, 2, 0
4 timesHigh pressure (MPa)4
1.52 MPa → 1, 5, 2
5 times Low pre
ssure (MPa)5
0.43 MPa → 0, 4, 3
6 times Discharge temperature (Compressor 6
87 °C → 0, 8, 7
7 times Discharge temperature (Compressor 7
87 °C → 0, 8, 7
8 times IPM temperature (Compressor 1) 8
87 °C → 0, 8, 7
9 times IPM temperature (Compressor 2)9
87 °C → 0, 8, 7
10 times CT sensor value
(Compressor 1) A
2 A → 0, 2, 0
11 times CT sensor value (Compressor 2)B
2 A → 0, 2, 0
12 times Suction temperature C
-42 °C → -, 4, 2
13 times COND OUT temperautre D
-42 °C → -, 4, 2
14 timesTemperature of liquid pipe E
-42 °C → -, 4, 2
15 times TOP tempera
ture (Compressor 1) F
-42 °C → -, 4, 2
16 times TOP temperature (Compressor 2)G
-42 °C → -, 4, 2
17 timesWater temperature H
-42 °C → -, 4, 2
18 times EVI inlet temperature I
-42 °C → -, 4, 2
19 times EVI outlet temperature J
-42 °C → -, 4, 2
20 timesMain EEV 1 stepK
2000 st
eps → 2, 0, 0
21 timesMain EEV2 stepL
2000 steps → 2, 0, 0
22 times EVI EEV stepM
300 steps → 3, 0, 0
23 times HR EEV stepN
2000 steps → 2, 0, 0
24 times- O -
25 times Current frequency of the compressor P
120 Hz → 1,2,0
26 times Current frequency of th
e compressor Q
120 Hz → 1,2,0
27 times Suction 2 temperature R
-42 °C → -, 4, 2
28 timesAddress of master indoor unit S
When master indoor unit is not set → BLANK, N, D
When indoor unit No.1 is set as master indoor unit →0, 0, 1
29 timesTemperature of control box T
-42 °C → -, 4, 2
㽞AM072/096/120/192HXWA66
ఐ When you install the product, optional function for outdoor unit must be set in compliance with installation conditions.
ఐ SW version, View mode 2 and address of the indoor unit, press and hold for three seconds to enter the K4.
(Information will be d
isplayed in following order. Main-Hub-INV1-INV2 FAN1-FAN2-EEP-Automatically assigned address -
manually assigned address.)
View mode 2
K4
(Number of press)
KEY operation KEY operation
Display on Page
Page 1 Page 2
1
TIME Main version Main version Main Version(ex. 1412)
2
TIMES HUB version HUB version HUB Version(ex. 1412)
3
TIMES Water HUB version Water HUB version HUB2 Version(ex. 1412)
4
TIMES Inverter1 version Inverter1 version INV1 Version(ex. 1412)
5
TIMES Inverter2 version Inverter2 version INV2 Version(ex. 1412)
6
TIMES EEPROM version EEPROM version EEPROM Version(ex. 1412)
7
TIMES
The device receives
automatic address
The device receives
automatic address
AUTO
SEG1,2 SEG3,4
Indoor unit : "A","0"
MCU : "C","1"
Adress(ex. 07)
8
TIMES
The device receives
a manual address
The device receives
a manual address
MANU
SEG1,2 SEG3,4
Indoor unit : "A","0" Adress(ex. 15)
How to check the view mode using a tact switch (cont.)