Troubleshooting
4-20 Samsung Electronics
Initial Tracking (Communication Check-up) - Display for Problem
1. For the display module of the outdoor unit, there are dierences in the contents displayed depending on whether the relevant outdoor
unit is a master unit or a sub unit.
1) Master Unit
The outdoor unit Micom attempts communication with the indoor unit connected to the communication cable (F1/F2) when the power is turned on.
Basic segment display
Step Display content Display
At initial power input
Checking segment
display
SEG1 SEG2 SEG3 SEG4
"8" "8" "8" "8"
While setting
communication
between indoor and
outdoor unit
(Addressing)
Number of
connected indoor
units
SEG1 SEG2 SEG3, 4 SEG3, 4
"A" "d"
Number of communicated units
Refer to "View Mode" for
communication address
After communication
setting
(usual occasion)
Transmit/
Reception address
SEG1 SEG2 SEG3, 4 SEG3, 4
I/U : A
MCU : C
I/U : 0
MCU : 1
Reception address
(in decimal number)
I/U : Indoor unit
If the number of indoor units set by the outdoor unit is not in accordance with the number of indoor units that succeeded with
communication, then the four displaying parts will display .
2) Sub(Slave) Unit
The two left hand displays show its own address and the two right hand displays show the outdoor unit's address.
Main address : C8, Sub1 address : C9, Sub2 address : CA, Sub3 address : CB
2
. The number of the indoor Units Connected to the outdoor unit can be congured by using the indoor unit installation quantity setup switch.
g
SEG1
a f
G1
G2
b c e d
SEG2
g
SEG3
a f
G1
G2
b c e d
SEG4
Outdoor Unit Display Parts
3. If the quantity of the indoor units congured with the indoor unit installation quantity setup switch does not match the quantity of the
indoor units found during the tracking process, E201 and U200 will be displayed in order on the display module.
4. When you install more than one MCU, set the quantity of installed MCU.
Indoor Unit Installation Quantity Setup Switch
The following is an example of how to use the switch according to the number
of indoor unit installations. The maximum number of possible indoor unit con-
nections is 64.
10s Digit
(0~9)
1s Digit
(0~9)
3Units Connected 17Units Connected 31Units Connected 64Units Connected
10s Digit
0
1s Digit
3
10s Digit
1
1s Digit
7
10s Digit
3
1s Digit
1
10s Digit
6
1s Digit
4
Indoor Unit
Installed
Quantity
MCU
Installed
Quantity